LINETRAXX® NGRM700

LINETRAXX® NGRM700

The NGRM700 Neutral Grounding Resistor Monitor detects grounding-resistor failures and ground faults and monitors line voltages. It is intended for use in high-resistance grounded commercial and industrial power systems. It is an advanced device that allows monitoring of :

  • Current through the neutral-grounding resistor (NGR)
  • Voltage between the transformer or generator neutral point and ground (voltage drop across the NGR)
  • NGR failure (open and short), including failure of connections between neutral and ground
  • Line-to-line and line-to-ground voltages

The NGRM500 can display the measured values, including current and voltage harmonics on the human machine interface (HMI). Users are able to select filters for ground-fault current and NGR voltage to prevent nuisance operation in noisy applications. A benefit to many users is the multilingual user interface that allows the comfort of reading values and programming in your native language.

It is designed for easy retrofit with a panel mountable human-machine interface (HMI). If preferred, the relay can easily be programmed via the built-in webserver. NGRM700’s can easily connect to a supervisory system with Modbus TCP/IP or RTU communications.

For generator or transformer grounding applications at extreme altitudes, the NGRM700 features a 5,000 m above sea level capability.

It is an ideal solution that is easy to retrofit into existing HRG applications or factory-install in new HRG packages. Capabilities extend to 25 kV and up to 100 A.

The NGRM700 allows the user to meet Canadian requirements. It can be used to perform the functions required by Rule 10-302, Use of Impedance Grounded Systems, of the CE Code, C22.1-21, Section 10, Grounding and Bonding.

  • Features
  • Accessories
  • Ordering information
  • Downloads
  • Determination of RNGR with passive and active measurement methods
  • Continuous monitoring of the RNGR even if the installation is de-energized
  • Alarm or trip on ground fault
  • Monitoring of the current INGR
  • Monitoring of the voltage UNGR
  • Phase-to-ground fault indication (optional; up to 690 V direct coupling, otherwise via potential transformers)
  • Ethernet communication
  • Web server
  • Language selection (German, English GB and US, Spanish, French)
  • Test button (internal, external) with/without tripping
  • FFT analysis of the measuring signals
  • Pulser for manual ground fault location
  • Relay for detection of ground faults and resistor faults
  • Relay for shutdown of the installation after a configurable time
  • Can be combined with RCMS… for automatic shutdown of feeders
  • Graphical user interface
  • Wide supply voltage range (24 to 240 VAC/VDC)
  • Range of use up to 5000 m AMSL
  • Fault/history memory
  • Analog output of measured values (0…10 V, 4…20 mA, etc., selectable parameters)
  • Detachable HMI for door mounting
  • Password protection
  • Tripping on RMS, fundamental component signal or harmonics
  • Detection of AC and DC ground faults

Optional accessories for LINETRAXX® NGRM700

CD-series coupling device
Voltage UsysTypeArt. No.
400…690 VCD1000B98039010
400…1000 VCD1000-2B98039053
1000…4200 VCD5000B98039011
4300…14550 VCD14400B98039054
14551…25000 VCD25000B98039055


Measuring current transformer

Voltage/CurrentTypeArt. No.
AC up to 25 AW20
W35
W60
W0-S20
W1-S35
W2-S70
B98080003
B98080010
B98080018
B911787
B911731
B911732
AC/DC up to 10 ACTUB103-CTBC35B78120030
AC/DC up to 25 ACTUB103-CTBC60
CTUB103-CTBC120
B78120031
B78120032


Voltage supply for measuring current transformers CTUB103…

Typemax. connected measuring current transformersArt. No.
STEP-PS/1 AC/24 DC/0.52B94053110
STEP-PS/1 AC/24 DC/1.757B94053111
STEP-PS/1 AC/24 DC/4.217B94053112


Clamp - Included with NGRM700

NameTypeArt. No.
FP200-NGRM clamp (set of 2)Metal screw B91067907

Variants of LINETRAXX® NGRM700


TypeSupply voltage US/Frequency range HzArt. No.
NGRM700AC 24…240 V, 40…70 Hz
DC 24…240 V
B94013700
Accessory for FP200-NGRM: Transparent front cover 144x72 (for IP65)*B98060005
*When using the "transparent front cover 144x72 (IP 65)" the cutout in the switchboard cabinet must be extended in height from 66 mm to 68 mm (+0.7/-0 mm).
The degree of protection IP65 applies only to the user interface FP200-NGRM when using the front cover. The degree of protection for the complete device is still IP30.

Downloads for LINETRAXX® NGRM700

Category

Language

Category Product Language Size Download